FAIRS
PV ROME MEDITERRANEAN 2010 08-09-2010
    HOME  ITALIAN       |       
I C C | ITALIAN CABLE COMPANY
   
 
CATALOGUE > H05GG-F
Download data sheet
 
FLEXIBLE CABLES EVA INSULATED, HEAT RESISTANT FOR TEMPERATURES UP TO 110°C .
 
1- Flexible tin plated copper class 5 CEI EN 60228
2- Rubber type EVA EI3
3- Rubber type EM4
 
 STANDARDS APPROVALS PACKAGING  
CEI 20-19/11
HD 22
 
  CHARACTERISTICS
 
Operating Temperature: +0°C ÷ +110° C on the conductor
Rated voltage: 300/500 V
Max. temperature of short circuit: 250° C on the conductor (max. duration 5 seconds)
Min. bending radius: Mobile installation: 4 x outer diameter
Fixed installation: 3 x outer diameter
   
  APPLICATIONS
 
 
Section Max. diam.
of conductor
Insulation
thickness*
Sheat
thickness*
Outer
diameter

Max. resistance
at 20°C

Cable
weight
mm² mm mm mm mm ohms/km kg/km
2x0,75 0,21 0,6 0,8 6,3 26,7 53
2x1,00 0,21 0,6 0,9 6,8 20,0 64
2x1,5 0,26 0,8 1,0 8,3 13,7 95
2x2,5 0,26 0,9 1,1 9,8 8,21 140
3G0,75 0,21 0,6 0,9 6,8 26,7 65
3G1,00 0,21 0,6 0,9 7,2 20,0 77
3G1,5 0,26 0,8 1,0 8,8 13,7 115
3G2,5 0,26 0,9 1,1 10,4 8,21 170
3G4 0,31 1 1,2 12,2 5,09 240
3G6 0,31 1 1,4 13,6 3,39 320
4G0,75 0,21 0,6 0,9 7,4 26,7 80
4G1,00 0,21 0,6 0,9 7,8 20,0 95
4G1,5 0,26 0,8 1,1 9,8 13,7 145
4G2,5 0,26 0,9 1,2 11,5 8,21 210
4G4 0,31 1
1,3 13,5 5,09 300
4G6 0,31 1
1,5 15,1 3,39 405
5G0,75 0,21 0,6 1,0 8,3 26,7 100
5G1,00 0,21 0,6 1,0 8,7 20,0 115
5G1,5 0,26 0,8 1,1 10,7 13,7 170
5G2,5
0,26 0,9 1,3 12,8 8,21 255
  *medio/average